AElE/Chapter 9/Read MCQs
📖 Back to Study Notes
9

Chapter 9 · MCQ Read Mode

Power System Analysis

AELE09·60 Total MCQs
Question 1 of 60Transmission Line Parameters

The series parameters of a transmission line equivalent circuit are:

ACapacitance and conductance
BResistance and inductance
COnly capacitance
DOnly conductance
Answer is hidden
Question 2 of 60Transmission Line Parameters

GMR (Geometric Mean Radius) is used in transmission line calculations to account for:

AThe spacing between phase conductors
BThe internal flux linkage of a conductor, giving an equivalent radius for inductance calculation
CThe capacitance to ground only
DThe corona inception voltage
Answer is hidden
Question 3 of 60Transmission Line Parameters

Capacitance calculation for a transmission line uses:

AGMR instead of actual conductor radius
BThe actual conductor radius (not GMR), since capacitance depends on the external electric field
CNeither GMD nor conductor radius
DOnly the conductor's internal flux linkage
Answer is hidden
Question 4 of 60Transmission Line Parameters

Transposition of transmission line conductors is performed to:

AIncrease unbalanced mutual inductance/capacitance among phases
BEqualize mutual inductance/capacitance among phases despite unsymmetrical spacing
CEliminate the need for any per unit calculations
DIncrease corona loss intentionally
Answer is hidden
Question 5 of 60Transmission Line Parameters

Skin effect in an AC conductor refers to: resistance

AUniform current distribution across the conductor cross-section
BHigher current density near the conductor surface, reducing usable cross-section and increasing effective AC
CA reduction in AC resistance compared to DC resistance
DAn effect that only occurs at DC
Answer is hidden
Question 6 of 60Transmission Line Parameters

Proximity effect in transmission line conductors becomes more significant when:

AConductors are widely spaced
BConductors are closely spaced, so nearby conductors' magnetic fields distort current distribution
CThe system operates at DC only
DConductor radius is very large with no nearby conductors
Answer is hidden
Question 7 of 60Transmission Line Parameters

Corona inception voltage is the threshold at which:

AThe conductor physically melts
BThe surface voltage gradient becomes sufficient to ionize the surrounding air
CThe line loses all capacitance
DThe conductor's DC resistance becomes zero
Answer is hidden
Question 8 of 60Transmission Line Parameters

Bundled conductors are used on EHV lines primarily to:

AIncrease corona loss and radio interference
BIncrease effective conductor diameter, reducing surface voltage gradient and thus corona loss
CReduce the line's current-carrying capacity
DEliminate the need for transposition
Answer is hidden
Question 9 of 60Transmission Line Parameters

In the per unit system, base impedance is calculated as:

ABase MVA divided by base kV
B(Base kV)² divided by base MVA
CBase kV multiplied by base MVA
DBase kV squared multiplied by base MVA
Answer is hidden
Question 10 of 60Transmission Line Parameters

A single-line diagram is used to represent a power system because:

AEach phase must be shown separately for accuracy
BUnder balanced three-phase conditions, all three phases are identical, so one line suffices
CIt eliminates the need for any impedance diagram
DIt applies only to single-phase systems
Answer is hidden
Question 11 of 60Performance of Transmission Line

A short transmission line (up to ~80 km) is typically modeled using:

AOnly shunt capacitance
BLumped series impedance only, with shunt capacitance neglected
CA fully distributed-parameter model
DOnly a shunt conductance
Answer is hidden
Question 12 of 60Performance of Transmission Line

A long transmission line (greater than about 250 km) is most accurately modeled using:

AA lumped series impedance only
BA distributed-parameter model using hyperbolic functions of the propagation constant and length
CNo electrical model at all
DThe same nominal-π model as a medium line, with no modification
Answer is hidden
Question 13 of 60Performance of Transmission Line

For a symmetrical transmission line represented by ABCD parameters:

AA and D are always different
BA = D
CB and C are always zero
DAD + BC = 0
Answer is hidden
Question 14 of 60Performance of Transmission Line

For a passive, reciprocal two-port network represented by ABCD parameters, the identity that must hold is:

AAD + BC = 1
BAD − BC = 1
CA + D = 0
DBC = 0 always
Answer is hidden
Question 15 of 60Performance of Transmission Line

In the ABCD parameter representation, the constant B has units of:

ASiemens (mhos)
BOhms (impedance)
CNo units (dimensionless)
DWatts
Answer is hidden
Question 16 of 60Performance of Transmission Line

The Ferranti effect occurs when:

AA heavily loaded line has receiving-end voltage lower than sending-end voltage
BA lightly-loaded or no-load long line has receiving-end voltage exceeding sending-end voltage
CA line is perfectly loaded at its surge impedance loading
DOnly short lines are involved
Answer is hidden
Question 17 of 60Performance of Transmission Line

Surge Impedance Loading (SIL) is defined as the power delivered when a line is terminated in a resistive load equal to:

AIts series resistance only
BIts surge (characteristic) impedance, ZC = √(L/C)
CZero ohms (a short circuit)
DInfinite impedance (open circuit)
Answer is hidden
Question 18 of 60Performance of Transmission Line

At Surge Impedance Loading, a transmission line operates at:

AA highly lagging power factor with large voltage drop
BUnity power factor with a flat voltage profile along the line
CZero power factor
DMaximum possible voltage rise at the receiving end
Answer is hidden
Question 19 of 60Performance of Transmission Line

Loading a long transmission line below its SIL tends to cause:

AVoltage drop toward the receiving end
BVoltage rise toward the receiving end, as the capacitive (Ferranti-like) effect dominates
CNo change in voltage profile under any condition
DImmediate line tripping
Answer is hidden
Question 20 of 60Performance of Transmission Line

Loading a long transmission line above its SIL tends to cause:

AVoltage rise toward the receiving end
BVoltage drop toward the receiving end, as the inductive effect dominates
CThe line to behave purely capacitively
DNo relationship between loading and voltage profile
Answer is hidden
Question 21 of 60Fault Calculations

The method of symmetrical components resolves an unbalanced 3-phase phasor set into:

AA single balanced set only
BPositive, negative, and zero sequence balanced sets
COnly positive and negative sequence sets
DFour sequence sets
Answer is hidden
Question 22 of 60Fault Calculations

Positive sequence components have a phase rotation that is:

AOpposite to the normal system (a-c-b)
BThe same as the normal system (a-b-c)
CIdentical in all three phases with no rotation
DUndefined
Answer is hidden
Question 23 of 60Fault Calculations

Zero sequence current requires, for it to flow in a power system:

ANo special path at all
BA return path, such as a grounded neutral or earth connection
COnly a balanced three-phase load
DA purely resistive load
Answer is hidden
Question 24 of 60Fault Calculations

In an ungrounded (or high-impedance grounded) system, a single line-to-ground fault typically results in:

AVery high ground fault current with no voltage rise
BLimited fault current, but possible significant voltage rise on the healthy phases
CNo fault current and no voltage change at all
DImmediate destruction of all connected equipment
Answer is hidden
Question 25 of 60Fault Calculations

A single line-to-ground (L-G) fault is analyzed by connecting the three sequence networks:

AIn parallel
BIn series
CCompletely disconnected from each other
DOnly the positive sequence network is used
Answer is hidden
Question 26 of 60Fault Calculations

A line-to-line (L-L) fault, with no ground involvement, does NOT involve:

AThe positive sequence network
BThe negative sequence network
CZero sequence current flow
DAny sequence network at all
Answer is hidden
Question 27 of 60Fault Calculations

A double line-to-ground (L-L-G) fault is represented by connecting the three sequence networks:

AIn series
BIn parallel
CUsing only the zero sequence network
DUsing only the negative sequence network
Answer is hidden
Question 28 of 60Fault Calculations

A three-phase fault (L-L-L) is unique among fault types in that it:

ARequires all three sequence networks connected in series
BIs the only balanced fault type, analyzable using only the positive sequence network
CNever produces significant fault current
DCannot occur in practice
Answer is hidden
Question 29 of 60Fault Calculations

Among common fault types, the three-phase fault generally produces:

AThe lowest fault current on most systems
BThe highest fault current on most systems
CExactly the same fault current as an L-G fault always
DNo fault current at all
Answer is hidden
Question 30 of 60Fault Calculations

A solidly (effectively) grounded system, compared to an ungrounded system, during a ground fault typically exhibits:

ALower ground fault current and higher healthy-phase overvoltage
BHigher ground fault current but more limited transient overvoltage on healthy phases
CIdentical behavior to an ungrounded system in all respects
DNo ground fault current at all
Answer is hidden
Question 31 of 60Load Flow

In the Y-bus matrix, the diagonal element Yii represents:

AThe negative of the admittance between bus i and bus j
BThe sum of all admittances connected to bus i
CAlways zero
DThe system's total generation
Answer is hidden
Question 32 of 60Load Flow

In the Y-bus matrix, an off-diagonal element Yij (for buses i and j with no direct connection) is:

AAlways equal to the diagonal element
BZero
CAlways a large positive number
DEqual to the system's base MVA
Answer is hidden
Question 33 of 60Load Flow

A slack (swing) bus in a load flow study is characterized by:

ASpecified real and reactive power, with voltage to be solved
BSpecified voltage magnitude and angle, absorbing the system's power balance/losses
CSpecified voltage magnitude and real power only
DNo specified quantities at all
Answer is hidden
Question 34 of 60Load Flow

A PV (generator) bus in a load flow study has which quantities specified?

AReal and reactive power
BVoltage magnitude and real power
CVoltage magnitude and angle
DNothing is specified
Answer is hidden
Question 35 of 60Load Flow

The Gauss-Seidel load flow method updates bus voltages by:

AUsing only values from the previous complete iteration
BUsing the most recently computed values of other bus voltages within the same iteration
CSolving a full Jacobian matrix at every iteration
DIgnoring the power balance equations entirely
Answer is hidden
Question 36 of 60Load Flow

A key drawback of the Gauss-Seidel method for load flow is:

AExcessive memory requirement per iteration
BSlow (linear) convergence, requiring a relatively large number of iterations
CIts complete inability to converge on any system
DRequiring a Jacobian matrix at every iteration
Answer is hidden
Question 37 of 60Load Flow

The Newton-Raphson load flow method linearizes the power flow equations at each iteration using:

AA random guess with no mathematical basis
BThe Jacobian matrix of partial derivatives
COnly the Y-bus diagonal elements
DA fixed table of pre-computed values
Answer is hidden
Question 38 of 60Load Flow

Compared to Gauss-Seidel, the Newton-Raphson method generally offers:

ASlower convergence for large systems
BFaster (quadratic) convergence near the solution, requiring fewer iterations for large systems
CNo difference in convergence behavior
DConvergence only for very small systems
Answer is hidden
Question 39 of 60Load Flow

The Fast Decoupled Load Flow method simplifies computation by exploiting the typical relationship that:

AReal power depends mainly on voltage magnitude and reactive power on voltage angle
BReal power depends mainly on voltage angle and reactive power on voltage magnitude
CReal and reactive power are entirely unrelated to voltage
DVoltage magnitude has no effect on either real or reactive power
Answer is hidden
Question 40 of 60Load Flow

Newton-Raphson is generally preferred over Gauss-Seidel for large-scale practical power system load flow studies because of its:

ALower computational cost per iteration
BSuperior (quadratic) convergence behavior, despite higher cost per iteration
CComplete elimination of the need for a Y-bus matrix
DRequirement of fewer bus classifications
Answer is hidden
Question 41 of 60Stability Analysis

Steady state stability limit refers to the maximum power transfer possible:

AFollowing a sudden large disturbance
BWithout loss of synchronism under small, slow (quasi-static) disturbances or load changes
COnly during a three-phase fault
DWith no relationship to synchronism at all
Answer is hidden
Question 42 of 60Stability Analysis

Transient stability assessment following a disturbance typically focuses on:

AOnly the system's behavior after 10 minutes
BThe first swing (typically around 1 second) after the disturbance
COnly steady-state conditions decades later
DA period with no relevance to fault clearing time
Answer is hidden
Question 43 of 60Stability Analysis

The swing equation relates a generator's angular acceleration to:

AOnly its rated voltage
BThe accelerating power — the difference between mechanical input power and electrical output power
COnly the system's base MVA
DThe line's series resistance alone
Answer is hidden
Question 44 of 60Stability Analysis

If a generator's mechanical input power exceeds its electrical output power, the rotor:

ADecelerates, causing δ to decrease
BAccelerates, causing δ to increase
CRemains at exactly constant speed with no change in δ
DImmediately loses synchronism
Answer is hidden
Question 45 of 60Stability Analysis

The equal area criterion assesses transient stability by comparing:

AOnly the fault duration to an arbitrary fixed value
BThe accelerating area to the available decelerating area on the power-angle curve
CThe system's total installed capacity to its peak load
DOnly the generator's inertia constant in isolation
Answer is hidden
Question 46 of 60Stability Analysis

The equal area criterion is commonly used to determine:

AThe system's total generation capacity
BThe critical clearing angle/time for a fault
CThe steady state voltage regulation of a line
DThe corona inception voltage
Answer is hidden
Question 47 of 60Stability Analysis

Fast fault clearing improves transient stability primarily by:

AIncreasing the accelerating area experienced during the fault
BReducing the accelerating area experienced during the fault, since the fault is removed sooner
CHaving no effect on system stability
DIncreasing the fault current magnitude
Answer is hidden
Question 48 of 60Stability Analysis

Which of the following is a stability enhancement technique?

ASlowing down circuit breaker operation deliberately
BInstalling power system stabilizers (PSS) and fast-responding excitation systems (AVR)
CRemoving all series compensation from long lines
DDisabling automatic reclosing entirely
Answer is hidden
Question 49 of 60Stability Analysis

Voltage collapse is best described as: power support

AA sudden loss of generator synchronism only
BA progressive, uncontrollable decline in system voltage, often under heavy loading with insufficient reactive
CA condition that always occurs simultaneously with rotor-angle instability and never independently
DAn event unrelated to reactive power demand
Answer is hidden
Question 50 of 60Stability Analysis

Reducing the transfer reactance of a transmission path (e.g. via series compensation) generally helps stability by:

AIncreasing the accelerating area for a given fault
BIncreasing the power transfer capability and available decelerating area on the power-angle curve
CHaving no effect on the power-angle relationship
DReducing the system's steady state stability limit
Answer is hidden
Question 51 of 60Voltage Control and VAR Compensation

Real power flow through a predominantly reactive transmission line is primarily controlled by:

AThe voltage magnitude difference between the two buses
BThe angle difference (δ) between the two bus voltages
CThe line's shunt capacitance alone
DThe ambient temperature
Answer is hidden
Question 52 of 60Voltage Control and VAR Compensation

Reactive power flow through a predominantly reactive transmission line is primarily controlled by:

AThe angle difference between the two bus voltages
BThe voltage magnitude difference between the two buses
CThe line's series resistance only
DThe system frequency alone
Answer is hidden
Question 53 of 60Voltage Control and VAR Compensation

The angle-real-power / magnitude-reactive-power decoupling is the physical basis for:

AThe Gauss-Seidel method exclusively
BThe Fast Decoupled Load Flow method and the practice of using VAR injection for local voltage control
CSymmetrical component analysis
DThe equal area criterion
Answer is hidden
Question 54 of 60Voltage Control and VAR Compensation

Series compensation of a transmission line primarily works by:

AAdding shunt capacitance at the receiving end
BReducing the line's effective series reactance, increasing real power transfer capability
CIncreasing the line's series resistance
DRemoving all reactive elements from the line
Answer is hidden
Question 55 of 60Voltage Control and VAR Compensation

A key risk associated with series capacitor compensation is:

AReduced power transfer capability
BSub-synchronous resonance (SSR) with nearby generator shafts
CComplete elimination of voltage drop with no downside
DGuaranteed improvement in all cases with no design considerations
Answer is hidden
Question 56 of 60Voltage Control and VAR Compensation

Shunt capacitor banks connected at a bus primarily serve to:

AAbsorb reactive power, lowering voltage
BSupply reactive power, raising voltage and supporting power factor
CIncrease the line's series reactance
DProvide the primary means of real power flow control
Answer is hidden
Question 57 of 60Voltage Control and VAR Compensation

Shunt reactors are typically used at the receiving end of a lightly-loaded long line to:

AFurther raise the already-elevated voltage caused by the Ferranti effect
BAbsorb reactive power and counter the voltage rise caused by the Ferranti effect
CIncrease real power transfer capability
DReplace the need for any series compensation
Answer is hidden
Question 58 of 60Voltage Control and VAR Compensation

Compared to fixed or mechanically-switched shunt compensation, dynamic devices such as SVC/STATCOM offer:

ASlower, less precise reactive power control
BRapid, continuously variable reactive power control, offering superior voltage regulation and stability support
CNo ability to vary reactive power output
DOnly real power control capability
Answer is hidden
Question 59 of 60Voltage Control and VAR Compensation

Maximum real power transfer over a line (for a given voltage magnitude) generally occurs near an angle difference of:

A0°
B90°
C180°
D270°
Answer is hidden
Question 60 of 60Voltage Control and VAR Compensation

A synchronous condenser used for VAR compensation is essentially:

AA static capacitor bank with no moving parts
BAn over-excited synchronous motor running unloaded, supplying reactive power
CA purely resistive shunt element
DA device that can only absorb, never supply, reactive power
Answer is hidden
← PREVIOUS CHAPTERCh 8: Utilization of Electrical Energy NEXT CHAPTER →Ch 10: Project Planning, Design and Implementation