1
This section covers the computation of series and shunt parameters of transmission line equivalent circuits, the concepts of GMD and GMR, proximity and skin effects, corona phenomena, and per unit system representation.
2
Series & Shunt Parameters A transmission line's series parameters are resistance (R, ohmic loss) and inductance (L, from the magnetic flux linking the conductors); its shunt parameter is capacitance (C, from the electric field between conductors and ground/each other), with shunt conductance (leakage) usually neglected.
3
Line inductance per phase depends on conductor geometry, expressed via the Geometric Mean Radius (GMR) — an equivalent radius accounting for internal flux linkage of a (possibly bundled/stranded) conductor — and the Geometric Mean Distance (GMD) — the equivalent spacing between phase conductors for unsymmetrically-spaced or transposed lines:
4
Line capacitance per phase similarly depends on conductor radius and GMD:
5
C ∝ 1/ln(GMD/r), where r is the actual conductor radius (capacitance calculation uses actual radius, not GMR, since it depends on the external electric field, not internal flux).
6
Transposition of conductors (cyclically interchanging phase positions along the line) equalizes the mutual inductance/capacitance among phases despite unsymmetrical spacing, using GMD as the equivalent symmetrical spacing.
7
Proximity Effect & Skin Effect Effect Description Skin effect At AC, current density is higher near the conductor surface and lower at the core, effectively reducing the usable cross-section and increasing effective AC resistance compared to DC resistance; increases with frequency and conductor size Proximity effect Current distribution within a conductor is further distorted by the magnetic field of a nearby current- carrying conductor, also increasing effective AC resistance; more significant when conductors are closely spaced Corona Corona is a partial electrical discharge (ionization of air) occurring around a conductor when the surface voltage gradient exceeds the critical (corona inception) voltage, a threshold depending on conductor radius, spacing, and atmospheric conditions (air density, humidity).
8
Corona power loss increases with system voltage above the inception threshold, and is influenced by conductor surface condition (smoother, larger-diameter or bundled conductors reduce corona), weather (worse in rain/fog/high humidity), and altitude (lower air density reduces breakdown strength, increasing corona).
9
Bundled conductors (two or more sub-conductors per phase) are commonly used on EHV lines specifically to increase the effective conductor diameter/reduce surface voltage gradient, reducing corona loss and radio interference.
10
Per Unit System Representation The per unit (p.u.) system expresses voltages, currents, powers, and impedances as fractions of chosen base quantities (typically base MVA and base kV), simplifying calculations across a network with multiple voltage levels via transformers.
11
Per unit impedance = actual impedance / base impedance, where base impedance = (base kV)² / base MVA; a consistent base MVA is used system-wide, while base kV is chosen appropriate to each voltage level (transformed by turns ratio across transformers).
12
A single-line diagram represents a three-phase balanced power system using one line (since all three phases are identical under balanced conditions), from which impedance and reactance diagrams are derived for load flow, fault, and stability studies — the impedance diagram includes resistance and reactance, while the reactance diagram (used for fault calculations) typically neglects resistance and static loads for simplicity.