This section covers the types, construction, characteristics, and application of fuses and isolators, and the role and selection of reactors in power systems.
2
Fuses Fuse Type Application Rewireable (kit-kat) fuse Simple, low-cost, replaceable fuse wire in a holder; used in low-voltage domestic/small installations Cartridge (HRC) fuse High Rupturing Capacity fuse, sealed element in a cartridge; faster, more reliable operation and higher breaking capacity than rewireable types; widely used in industrial/distribution circuits Drop-out fuse (expulsion fuse) Outdoor distribution fuse where the fuse carrier visibly drops/swings out after operation, providing clear visual indication and an isolation gap A fuse's key characteristic is its time-current characteristic (inverse relationship: higher fault current causes faster operation), and its breaking (rupturing) capacity (maximum fault current it can safely interrupt without damage/explosion).
3
Isolators An isolator (disconnector) is a mechanical switching device used to provide a visible, physical, and reliable open gap in a circuit for safe isolation during maintenance — it has no fault-current interrupting capability and must only be operated when the circuit is already de-energized (no-load, isolated by a circuit breaker first).
4
Common types include double-break and pantograph isolators for outdoor substations, distinguished by their opening mechanism/geometry.
5
Operating sequence rule: when de-energizing, the circuit breaker is opened first, then the isolator; when energizing, the isolator is closed first, then the circuit breaker — the isolator must never be operated under load.
6
Reactors A reactor is essentially a large inductor inserted into a power system to limit fault current, control reactive power, or reduce switching transients.
7
Series (current-limiting) reactors are connected in series with a feeder/bus to limit the magnitude of short- circuit current, reducing the required breaking capacity of downstream switchgear.
8
Shunt reactors are connected in parallel (typically at the receiving end of long transmission lines) to absorb excess reactive power (compensate for line charging capacitance), preventing excessive voltage rise under light-load conditions (Ferranti effect).
9
Reactor selection considers required reactance value, current/voltage rating, and system fault level.