1
This section covers the construction and working principle of synchronous machines (alternators and synchronous motors), excitation systems, the induced EMF equation, speed-frequency correlation, voltage/frequency regulation, losses and efficiency, and parallel operation/synchronizing.
2
Construction & Working Principle A synchronous machine has a field winding (usually on the rotor, excited by DC to produce the main field) and an armature winding (usually on the stator, where AC is induced/supplied), with the rotor driven at synchronous speed by a prime mover (as an alternator) or synchronized to the supply frequency (as a motor).
3
Rotor types: salient-pole rotors (protruding poles, used for low-speed machines like hydro alternators) and cylindrical (non-salient/round) rotors (uniform air gap, used for high-speed machines like turbo-alternators).
4
Excitation Systems Excitation Type Description DC excitation system A separate DC generator (exciter) supplies field current via slip rings AC excitation system An AC exciter with rotating rectifiers (brushless-style AC source) supplies field current Static excitation system Field current is obtained directly from the machine's own AC terminals via static (thyristor- based) rectifiers and slip rings Brushless excitation system A rotating AC exciter armature and rotating rectifier supply the field winding directly, eliminating slip rings and brushes entirely An Automatic Voltage Regulator (AVR) automatically adjusts the exciter's output (hence field current) to maintain the alternator's terminal voltage at the desired setpoint despite load changes.
5
Induced EMF, Speed-Frequency Correlation & Regulation Relation Formula/Meaning Speed- frequency relation f = PNₛ/120, where P is the number of poles and Nₛ is synchronous speed in rpm Induced EMF equation E = 4.44 fΦNKₖ (per phase), where f is frequency, Φ is flux per pole, N is turns per phase, and Kₖ is the winding factor Voltage regulation The percentage rise in terminal voltage when full load (at a given power factor) is removed, keeping speed and field excitation constant; indicates how much terminal voltage varies with load Losses, Efficiency, Parallel Operation & Synchronizing Losses comprise copper losses (armature, field), core losses, and mechanical (friction/windage) losses; efficiency is output/(output+losses), maximized under a similar variable-vs-constant loss balance as other rotating machines.
6
Synchronizing: connecting an alternator to the grid (or to another alternator/infinite bus) requires matching voltage magnitude, frequency, phase sequence, and phase angle before closing the connecting switch, to avoid damaging inrush currents.
7
Once connected to an infinite bus (a bus whose voltage and frequency are fixed, unaffected by the machine), an alternator's speed/frequency is fixed by the bus; adjusting its prime-mover input changes its power output (not speed), and adjusting its field excitation changes its reactive power output (not terminal voltage).
8
Synchronous Motors Working principle: a synchronous motor runs at exactly synchronous speed, locked in step with the rotating stator field, by the magnetic attraction between the rotor's DC-excited poles and the rotating stator field — it develops no net starting torque from a standstill and needs an external means to reach near- synchronous speed.
9
Starting methods: using an auxiliary/pony motor to bring it up to near-synchronous speed, or (most common) an induction-motor-type starting via a damper (amortisseur) winding, after which DC excitation is applied and the rotor pulls into synchronism.
10
Applications: constant-speed industrial drives, and specifically as a synchronous condenser (over- excited, running unloaded) to supply leading reactive power for power-factor correction/voltage support on a system.