This section covers transformer construction and types, the EMF equation, losses and efficiency, equivalent- circuit parameters from standard tests, voltage regulation, and three-phase, autotransformer and pulse transformer variants.
2
Construction & Types A transformer is a static device (no moving parts) that transfers electrical energy between two circuits via electromagnetic induction, changing voltage/current level while frequency stays the same.
3
Classified by turns ratio: step-up (raises voltage) or step-down (lowers voltage).
4
By construction: core- type or shell-type.
5
By application: power, distribution, or instrument transformers.
6
The core is built from thin, laminated silicon-steel sheets to reduce eddy-current loss.
7
EMF Equation & Operation EMF equation:
8
E = 4.44·f·N·Φₘ (applies to both primary and secondary, using their respective turns N).
9
Turns ratio: a = N₁/N₂ = V₁/V₂ = I₂/I₁ for an ideal transformer.
10
On no-load, the primary draws only a small magnetizing current to set up the core flux; under load, the secondary current's demagnetizing MMF is balanced by additional primary current.
11
Losses, Efficiency & Equivalent Circuit Tests Test Determines Open-circuit (OC) test Iron (core) loss, no-load current, and the shunt-branch parameters of the equivalent circuit Short-circuit (SC) test Copper loss and the equivalent series resistance/reactance of the equivalent circuit Copper loss (I²R) varies with load; iron loss (hysteresis + eddy current) is essentially constant, depending on flux/frequency.
12
Maximum efficiency occurs at the load where copper loss = iron loss.
13
Voltage regulation: the percentage change in secondary terminal voltage from no-load to full-load, expressed as a percentage of rated voltage.
14
Three-Phase Transformers & Special Types A three-phase transformer is built either from three single-phase units or one integrated three-phase core; standard winding connections include star-star, delta-delta, star-delta, and delta-star.
15
Autotransformer: uses a SINGLE winding shared between primary and secondary (electrically connected, not fully isolated) — smaller, cheaper, but offers no electrical isolation.
16
Pulse transformer: designed to transfer fast rise-time pulses with minimal distortion — used in digital/switching applications.