1
This section covers thermodynamic cycles for refrigeration, refrigeration system types, the functional requirements of cold storage for different perishable products, cooling load calculation, and classification of refrigerants.
2
Thermodynamic Cycles for Refrigeration The vapour compression cycle is the most common refrigeration cycle, consisting of four main processes: compression (compressor raises refrigerant pressure/temperature as a superheated vapour), condensation (heat rejected to ambient/cooling medium as vapour condenses to liquid at high pressure), expansion (throttling through an expansion valve/capillary, reducing pressure/temperature), and evaporation (refrigerant absorbs heat from the cold space, vaporizing at low pressure) — the cycle repeating continuously.
3
The vapour absorption cycle replaces the mechanical compressor with a thermally-driven absorption/generation process (using a refrigerant-absorbent pair, e.g. ammonia-water or water-lithium bromide), useful where waste heat or an alternative heat source (rather than electricity/mechanical work) is available to drive the cycle.
4
Refrigeration System Types Vapour compression systems: the dominant system type for most agricultural/food cold storage applications, using an electrically driven compressor; simpler control, widely available equipment and spares.
5
Vapour absorption systems: less common for typical farm-scale cold storage, but relevant where heat sources like biogas, solar thermal, or waste heat are available in place of reliable electricity.
6
Functional Requirements and Cooling Load Functional requirements for cold storage vary by product: different perishables require specific temperature and relative humidity ranges to maximize storage life while minimizing quality loss (chilling injury for some products if too cold, excessive moisture loss/wilting if too dry, condensation/decay if too humid); adequate air circulation is needed for uniform temperature distribution.
7
Calculation of cooling load for a cold store sums:
8
(1) product load (heat to be removed from the product to bring it to storage temperature, plus its respiration heat if it is a living, respiring commodity such as fresh fruit/vegetables), (2) transmission load (heat gain through walls/roof/floor by conduction, based on insulation U-value, area, and temperature difference), (3) infiltration/air-change load (heat gain from outside air entering via door openings/leakage), and (4) internal loads (lighting, fan motors, personnel, defrost heat) — the compressor/refrigeration system is then sized to remove this total load within the desired pull-down time.
9
Principle and design of a cold storage system includes selecting appropriate insulation thickness (to limit transmission load and condensation risk), evaporator/condenser sizing matched to the calculated load, and a control system maintaining the required temperature/humidity set-points.
10
Classification of Refrigerants Refrigerant Class Characteristics CFCs (chlorofluorocarbons) Historically common (e.g.
11
R-12), but ozone-depleting; now largely phased out under international agreements HCFCs (hydrochlorofluorocarbons) Lower ozone-depletion potential than CFCs but still ozone-depleting (e.g.
12
R-22); being phased out HFCs (hydrofluorocarbons) Non-ozone-depleting (e.g.
13
R-134a), but many have high global warming potential (GWP); increasingly regulated/phased down Natural/environment-friendly refrigerants Ammonia (NH3, efficient, toxic/flammable at high concentration, common in large industrial systems), CO2 (non-toxic, non-flammable, but requires high operating pressure), and hydrocarbons (e.g. propane/isobutane, efficient, flammable, used in small systems) — increasingly favored for low ozone-depletion and low global warming potential